MCCB 4P 125A 100kA Thermal Magnetic 250A Frame NM8N Chint
Chint NM8N 125A 4P MCCB features 100kA breaking capacity, thermal-magnetic trip unit with protected neutral and a 250A frame. For switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N 250H thermal magnetic moulded case circuit breaker, 125A 4-pole MCCB, 100kA MCCB
- Frame Size: 250 A
- Rated Current: 125 A
- Poles: 4-pole with protected neutral, 4C configuration
- Release Type: Thermal-magnetic trip unit for distribution protection
- Short-Circuit Breaking Capacity: 100 kA at 380/400/415 V AC
- Rated Operational Voltage: Up to 690 V AC, 50/60 Hz
- Rated Insulation Voltage: 1,000 V AC
- Rated Impulse Withstand Voltage: 8 kV
- Thermal Trip Adjustment: 0.7–1.0 times rated current
- Magnetic Trip Range: 7–12 times rated current for 125–160 A distribution protection
- Utilisation Category: A
- Isolation Function: Suitable for isolation
- Mechanical Life: Up to 25,000 operating cycles
- Electrical Life: Up to 10,000 operating cycles at 415 V AC and rated current
- Product Standard: IEC/EN 60947-2
- Dimensions (H x L x W): 157mm x 88.7mm x 140mm
- Weight: 2.5 kg
- 100 kA short-circuit breaking capacity at common low-voltage operating voltages
- Thermal-magnetic protection against overload and short circuit
- Protected neutral pole for four-pole distribution systems
- 250 A frame with a 125 A rated trip unit
- Suitable for switchboard incomer and mains protection applications
- Adjustable thermal and magnetic trip characteristics
- Zero arcing distance design
- Suitable for AC distribution systems up to 690 V
- Installation, adjustment and testing must be carried out by a licensed electrician in accordance with AS/NZS 3000, the switchboard assembly requirements and the manufacturer’s instructions. Confirm prospective fault current, discrimination, cable capacity and enclosure compatibility before commissioning.
- Switchboard mains and incomer protection
- Commercial and industrial distribution boards
- Three-phase four-wire electrical distribution systems
- Building services and plant-room power distribution
- Protection of feeders, cables and electrical equipment
- AS/NZS 60947.2 is the applicable Australian/New Zealand circuit-breaker standard for MCCBs of this type
- Electrical installation and connection should comply with AS/NZS 3000
- The completed switchboard assembly may also require assessment to AS/NZS 61439
- Durable moulded-case construction can extend service life and reduce replacement waste
- Metal conductive components can be recovered through appropriate electrical equipment recycling streams
- Resettable circuit protection avoids routine replacement of single-use fuses
- Supports safe, reliable electrical distribution and reduced equipment damage from overloads and short circuits
CHINT warranty policy states 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels; contract terms and Australian distributor conditions may vary.
Available through authorised CHINT distributors in Australia.