MCCB 4P 180A 70kA Thermal Magnetic 250A Frame NM8N Chint
Chint NM8N 180A 4P MCCB features 70kA breaking capacity, thermal-magnetic trip unit with protected neutral and a 250A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, MCCB, Thermal-Magnetic Circuit Breaker, Main Switchboard Breaker
- Product Type: Moulded case circuit breaker
- Series: NM8N-250Q
- Number of Poles: 4P
- Rated Current: 180A
- Frame Size: 250A
- Trip Unit: Thermal-magnetic
- Breaking Capacity: 70kA at AC 380/400/415V
- Rated Operational Voltage: Up to 690V AC, 50/60Hz
- Rated Insulation Voltage: 1000V AC
- Rated Impulse Withstand Voltage: 8kV
- Utilisation Category: A
- Neutral Protection: Protected neutral pole
- Connection Type: Fixed front connection
- Mechanical Endurance: Up to 15,000 operating cycles
- Electrical Endurance: Up to 6,000 operating cycles at rated current and AC 415V
- Isolation Function: Suitable for isolation
- Dimensions (H x L x W): 157mm x 88.7mm x 140mm
- Weight: 2.5 kg
- Four-pole protection for three-phase systems with neutral
- 180A thermal-magnetic overload and short-circuit protection
- 70kA ultimate short-circuit breaking capacity at up to 415V AC
- 250A frame accommodates a broad range of NM8N current ratings
- Suitable for switchboard incomer and mains protection applications
- Can be installed vertically or horizontally with top or bottom line entry
- Compatible with optional CHINT accessories including auxiliary contacts, shunt releases and undervoltage releases
- Installation, selection and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and the switchboard assembly requirements. Verify prospective fault current, discrimination, cable capacity, neutral arrangement and enclosure suitability before installation.
- Switchboard mains protection
- Main distribution boards
- Commercial and industrial electrical distribution
- Generator and transformer secondary protection
- Three-phase circuits requiring protected neutral switching and overcurrent protection
- AS/NZS IEC 60947.2 for low-voltage circuit-breakers
- AS/NZS 3000 for electrical installation and wiring requirements
- AS/NZS 61439 where installed as part of a low-voltage switchgear and controlgear assembly
- Long mechanical and electrical service life can reduce replacement frequency and equipment waste
- Metal and thermoplastic components may be recoverable through appropriate electrical equipment recycling streams
- Provides reliable fault protection that can help limit damage to downstream electrical equipment
CHINT general warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels. Contractual or Australian distributor warranty terms may vary.