Online UPS 10kVA 8kW 1Ph with 16x120Ah Batteries PowerSeries
PowerSeries GP online double conversion UPS features 10kVA 8kW, 1:1 single phase, 16x120Ah battery bank and generator compatibility. Ideal for critical loads.
Sign in
Please login to continue to your account.
Alternatively Known As: PowerSeries GP810-120-16 UPS, 10kVA Single-Phase Online UPS, GP Series UPS with A16T Battery Bank
- Model: GP810-120-16
- Capacity: 10kVA / 8kW
- Topology: Online double conversion with transformer
- Phase Configuration: Single-phase input and output, 1:1
- Input Voltage Range: 176–264V AC
- Input Frequency Range: 40–60Hz
- Maximum Input Current: 50A
- Output Voltage: 230V ±1%
- Output Frequency: 50Hz ±0.5%
- Output Waveform: PWM sine wave
- Output Power Factor: 0.8
- Output Harmonic Distortion: Less than 3% at linear load
- Transfer Time: 0 seconds
- Battery Type: Sealed lead-acid, maintenance-free
- Battery Configuration: 16 x 12V, 120Ah batteries
- Battery Bank Voltage: 192V DC
- Battery Recharge Time: Approximately 8 hours to 90% capacity after complete discharge
- Efficiency: Greater than 85% mains input to mains output
- Operating Temperature: 0–40°C
- Operating Humidity: 0–90% RH, non-condensing
- Noise Level: Less than 58dB
- Communications: RS232 and relay contact output
- Optional Communications: Internal SNMP card
- Bypass: Static and manual bypass
- Generator Compatibility: Suitable for generator-backed installations
- UPS Unit Weight: 182kg without batteries
- Battery Cabinet: BBGP-120-16, 1230 x 780 x 480mm, approximately 542kg
- Dimensions (H x L x W): 870mm x 600mm x 350mm
- Weight: 724 kg
- True online double-conversion protection for critical loads
- 10kVA / 8kW capacity with single-phase 1:1 configuration
- Supplied with a 192VDC battery bank comprising 16 x 120Ah sealed lead-acid batteries
- Zero-transfer-time operation during mains failure
- Pure sine-wave PWM output with less than 3% harmonic distortion at linear load
- Generator-compatible design for sites requiring extended backup resilience
- LCD and LED mimic panel for monitoring input, output, battery and load status
- Built-in static and manual bypass functions
- Overload, over-temperature, short-circuit and UPS fault protection
- RS232 and relay communications with optional SNMP remote monitoring
- Professional installation and commissioning are required. The UPS uses terminal connections and a high-voltage 192VDC battery bank, so installation should be completed by a licensed electrician or suitably qualified UPS technician in accordance with AS/NZS 3000 and the manufacturer's instructions. PSS hardwired products require commissioning by an approved and authorised PSS technician or contractor for warranty validity.
- Data centres and server rooms
- Telecommunications and network infrastructure
- Industrial control and automation systems
- Security, surveillance and access-control systems
- Point-of-sale and business-critical equipment
- Generator-backed critical-load installations
- Medical, commercial and infrastructure applications requiring uninterrupted single-phase power
- AS 62040.1:2019, applicable to UPS general and safety requirements
- AS 62040.3, applicable to UPS performance and testing
- AS/NZS 3000:2018, applicable to electrical installation, isolation, earthing and wiring
- AS/NZS 3820, applicable to essential safety requirements for in-scope electrical equipment
- Sealed lead-acid batteries can be recovered and recycled through appropriate battery recycling programs
- Online UPS protection can reduce equipment failure and electronic waste by protecting critical loads from voltage disturbances and outages
- Greater than 85% mains-to-output efficiency helps reduce operational energy losses compared with less efficient backup systems
- Replaceable battery-bank design can extend the service life of the UPS and reduce complete-system replacement waste
- Generator compatibility can support efficient integration with existing standby-power infrastructure
Standard PSS Distributors warranty is a 2-year return-to-base warranty from the original purchase date, subject to the published warranty conditions. Hardwired products must be commissioned by an approved and authorised PSS technician or contractor, and battery operation, storage and installation conditions must comply with manufacturer requirements.
Available through PowerSeries/PSS Distributors and authorised Australian distributors; contact the distributor for quotation, configuration and current lead time.
UPS Sizing Calculator
This calculator follows relevant Australian standards to ensure reliable and compliant performance. It provides an estimated recommendation based on user inputs.
Users must verify specifications before purchasing.