Online UPS 4kVA 3.2kW 1Ph with 16x120Ah Batteries PowerSeries
PowerSeries GP online double conversion UPS features 4kVA 3.2kW, 1:1 single phase, 16x120Ah battery bank and generator compatibility. Ideal for critical loads.
Sign in
Please login to continue to your account.
Alternatively Known As: PowerSeries GP Series UPS, GP804L120 UPS, 4kVA Online UPS, Single-Phase Double-Conversion UPS
- Capacity: 4kVA / 3.2kW
- Topology: Online double conversion with galvanic isolation
- Input: 176–264V AC, 40–60Hz
- Output: 230V AC ±1%, 50Hz ±0.5%
- Phase: Single phase, 1:1 configuration
- Power Factor: 0.8
- Output Waveform: PWM sine wave
- Output Distortion: Less than 3% for linear loads
- Battery Bank: 16 x 12V 120Ah sealed lead-acid batteries
- Nominal Battery Voltage: 192V DC
- Nominal Battery Energy: Approximately 23.04kWh
- Transfer Time: 0 seconds
- Efficiency: Greater than 85%
- Recharge Time: Approximately 8 hours to 90% after complete discharge
- Communications: RS-232; optional SNMP and relay interfaces
- Generator Compatibility: Supported
- Noise: Less than 58dB
- Operating Temperature: 0–40°C
- Relative Humidity: 0–90%, non-condensing
- Protection: Input surge filtering, electronic and fuse protection, overload, over-temperature and short-circuit protection
- Dimensions (H x L x W): 700mm x 635mm x 230mm
- Weight: 655 kg
- Continuous online double-conversion power conditioning for critical loads
- Transformer-based design with galvanic isolation
- Zero transfer time between mains and battery operation
- Pure sine-wave output with less than 3% total harmonic distortion for linear loads
- Generator-compatible operation
- Expandable runtime using external battery configurations
- LCD and LED status indication for voltage, frequency, load, battery and temperature
- Automatic transfer to bypass during overload or fault conditions
- Suitable for servers, telecommunications, security systems, industrial equipment and other critical loads
- Installation, battery connection, commissioning and hard-wiring should be completed by a licensed electrician or suitably qualified UPS technician. Provide appropriate isolation, earthing, ventilation, battery protection and electrical installation in accordance with AS/NZS 3000 and applicable UPS and battery-system requirements. The 192V DC, approximately 23.04kWh lead-acid battery bank requires controlled access and suitable battery-room or cabinet provisions.
- Critical IT and server-room loads
- Telecommunications and network infrastructure
- Security, access-control and surveillance systems
- Industrial control and automation equipment
- Point-of-sale and business systems
- Medical, laboratory and other sensitive electronic equipment where correctly specified
- Backup power systems integrated with standby generators
- AS/NZS 3000:2018 Electrical installations – Wiring Rules, applicable to installation, isolation, earthing and cabling
- AS IEC 62040.1, applicable to UPS safety requirements
- AS IEC 62040.2, applicable to UPS electromagnetic compatibility requirements
- AS IEC 62040.3, applicable to UPS performance and test requirements
- AS/NZS 5139:2019, applicable to the installation and safety of stationary battery systems connected to power-conversion equipment
- Sealed lead-acid batteries are recyclable through approved battery-recycling channels
- Online power conditioning can reduce disruption and premature failure of connected electronic equipment
- Generator compatibility can support efficient operation of standby power systems when correctly sized
- Transformer-based construction and replaceable battery architecture can extend service life and reduce complete-unit replacement waste
A specific POWERSERIES warranty policy for this UPS and battery package was not located. Confirm the applicable warranty period, exclusions, commissioning requirements and separate battery coverage with the supplier before purchase.
Available through POWERSERIES and authorised Australian distributors, subject to distributor stock and configuration availability.
UPS Sizing Calculator
This calculator follows relevant Australian standards to ensure reliable and compliant performance. It provides an estimated recommendation based on user inputs.
Users must verify specifications before purchasing.