Online UPS 4kVA 3.2kW 1Ph with 48x9Ah Batteries PowerSeries
PowerSeries GP online double conversion UPS features 4kVA 3.2kW, 1:1 single phase, 48x9Ah battery bank and generator compatibility. Ideal for critical loads.
Sign in
Please login to continue to your account.
Alternatively Known As: GP804 Online UPS, PowerSeries GP Series UPS, 4kVA Single-Phase Online UPS, Double-Conversion UPS
- Model: GP804
- Rated Capacity: 4kVA / 3.2kW
- Topology: Online double conversion with galvanic isolation
- Input: 176–264V AC, 40–60Hz, single phase
- Maximum Input Current: 20A
- Output Voltage: 230V ±1%
- Output Waveform: PWM sine wave
- Output Power Factor: 0.8
- Harmonic Distortion: Less than 3% at linear load
- Battery Type: Sealed lead-acid, maintenance-free
- Battery Configuration: 48 x 9Ah, 12V batteries
- Battery Bank Voltage: 576V DC
- Recharge Time: Approximately 8 hours to 90% capacity after complete discharge
- Efficiency: Greater than 85% mains input to mains output
- Transfer Time: 0 seconds
- Generator Compatibility: Yes
- Communication: RS232 and relay contact output
- Display: LCD and LED status indicators
- Protection: Input surge filtering, electronic and fuse protection, overload, over-temperature and short-circuit protection
- Noise Level: Less than 58dB
- Operating Temperature: 0–40°C
- Operating Humidity: 0–90% RH, non-condensing
- Dimensions (H x L x W): 700mm x 635mm x 230mm
- Weight: 240 kg
- True online double-conversion protection for critical loads
- Galvanic isolation between input and output
- Pure sine-wave output suitable for sensitive electronic and induction loads
- Generator-compatible operation
- Zero-transfer-time mains-to-battery operation
- Expandable battery runtime using external battery cabinets
- LCD and LED monitoring of voltage, frequency, load, battery status and temperature
- Pre-installed relay contacts for AC failure, low battery, UPS fault and bypass status
- Suitable for servers, IT infrastructure, surveillance, telecommunications and industrial equipment
- Installation, battery connection, commissioning and servicing should be performed by a licensed electrician or suitably qualified UPS technician. The hardwired UPS installation must comply with AS/NZS 3000 and manufacturer requirements, with appropriate ventilation, isolation, earthing and battery safety provisions.
- Critical IT and network infrastructure
- Servers and data-processing equipment
- Telecommunications and surveillance systems
- Industrial control and automation equipment
- Point-of-sale and business-critical systems
- Motors, air-conditioning equipment and other suitable induction loads
- Backup power systems requiring extended runtime and generator compatibility
- AS 62040.1:2019, Uninterruptible power systems — General and safety requirements for UPS
- AS/NZS 3000:2018, Electrical installations — Wiring Rules, applicable to permanent electrical installation and connection
- IEC/EN 62040-2 EMC requirements are referenced in the GP Series technical documentation
- Sealed lead-acid batteries can be recovered and recycled through approved battery recycling programs
- Replaceable external battery banks can extend system service life and reduce whole-unit replacement waste
- Generator compatibility can support efficient operation of critical loads during extended outages
- Long-life transformer-based construction is specified with an expected service life of approximately 15 years
- ECO or efficient operating modes may reduce energy consumption where supported by the configured system
PSS Distributors’ standard warranty is a 2-year return-to-base warranty from the original purchase date, subject to installation, operating and commissioning conditions. Transportation to the service base is generally excluded. Battery warranty coverage and commissioning requirements should be confirmed on the purchase documentation.
Available through PowerSeries/PSS Distributors and authorised Australian electrical and UPS distributors; confirm current stock and lead time before ordering.
UPS Sizing Calculator
This calculator follows relevant Australian standards to ensure reliable and compliant performance. It provides an estimated recommendation based on user inputs.
Users must verify specifications before purchasing.