Online UPS 6kVA 4.8kW 1Ph with 96x9Ah Batteries PowerSeries
PowerSeries GP online double conversion UPS features 6kVA 4.8kW, 1:1 single phase, 96x9Ah battery bank and generator compatibility. Ideal for critical loads.
Sign in
Please login to continue to your account.
Alternatively Known As: 6kVA Online UPS, 6000VA/4800W UPS, GP806 UPS, Single-Phase Online UPS, Battery-Backed Power Supply
- UPS Model: GP806
- Rated Capacity: 6000VA / 4800W
- Topology: Online double conversion
- Phase Configuration: 1:1 single phase input and output
- Output Voltage: 230V AC ±1%
- Input Voltage Range: 176–264V AC
- Input Frequency Range: 40–60Hz
- Output Frequency: 50Hz ±0.5%
- Output Waveform: PWM sine wave
- Output Power Factor: 0.8
- Battery Configuration: 96 x 12V 9Ah sealed lead-acid batteries
- Battery System Voltage: 192V DC
- Battery Bank Arrangement: Two BB-192T battery cabinets
- Input and Output Connection: Terminal connection
- Generator Compatibility: Yes
- Monitoring: LCD and mimic panel with input/output voltage, frequency, battery voltage, load and temperature indications
- Protection: Overload, over-temperature, short-circuit and UPS fault protection
- Operating Temperature: 0–40°C
- Operating Humidity: 0–90% RH, non-condensing
- Noise Level: Less than 58dB
- Dimensions (H x L x W): 700mm x 635mm x 700mm
- Weight: 395 kg
- True online double-conversion power protection for critical loads
- Continuous voltage and frequency conditioning
- Pure sine-wave PWM output suitable for sensitive electronic equipment
- Large external 192V battery system with 96 x 9Ah batteries
- Generator-compatible operation
- LCD and LED status indication
- Automatic transfer to bypass during overload or over-temperature conditions
- Pre-installed relay connections for monitoring and control
- Suitable for servers, telecommunications, security, point-of-sale and industrial equipment
- Installation, commissioning and battery connection should be completed by a licensed electrical contractor or suitably qualified UPS technician. The system is hardwired, contains high-energy 192V DC battery circuits and should be installed in accordance with AS/NZS 3000, the manufacturer's instructions and applicable UPS safety requirements.
- Server rooms and data centres
- Telecommunications and network equipment
- Security and surveillance systems
- Industrial control and automation equipment
- Point-of-sale systems
- Computer and storage equipment
- Critical infrastructure requiring conditioned backup power
- AS 62040.1:2019 — applicable Australian safety standard for uninterruptible power systems; product certification should be verified for the supplied configuration
- AS/NZS 3000 — electrical installation and wiring requirements applicable to hardwired UPS installation
- AS IEC 62040.3 — applicable UPS performance classification and testing reference
- Sealed lead-acid batteries can be recovered and recycled through approved battery-recycling channels
- Replaceable external batteries can extend the service life of the UPS and reduce equipment waste
- Online power conditioning can reduce the risk of damage and premature replacement of connected equipment
- Generator compatibility may support more efficient use of standby power infrastructure
No POWERSERIES-specific warranty term was publicly identified. Confirm the UPS and battery warranty period, commissioning conditions and battery coverage with the authorised Australian distributor before purchase.
Available through POWERSERIES and authorised Australian UPS distributors; configuration and lead time should be confirmed for the UPS and dual battery-cabinet package.
UPS Sizing Calculator
This calculator follows relevant Australian standards to ensure reliable and compliant performance. It provides an estimated recommendation based on user inputs.
Users must verify specifications before purchasing.