Technical Specifications
  • Power Rating: 2000VA / 2000W
  • UPS Topology: Online double conversion
  • Output Power Factor: 1.0
  • Input Voltage Range: 160–300VAC at 100% load
  • Input Voltage: 200/208/220/230/240VAC
  • Input Frequency: 50/60Hz
  • Input Connection: IEC C20
  • Output Connection: 4 x Australian outlets and 1 x IEC C19
  • Output Waveform: Pure sinewave
  • Output Voltage Regulation: ±1%
  • Transfer Time: 0ms mains to battery; 4ms line to bypass
  • Double Conversion Efficiency: 93%
  • ECO Mode Efficiency: 97%
  • Battery Configuration: 6 x 12V 7Ah
  • Rated Battery Voltage: 72VDC
  • Recharge Time: 3 hours to 90% capacity
  • Operating Temperature: 0–45°C
  • Operating Humidity: 0–95% non-condensing
  • Acoustic Noise: Less than 40dB at typical load
  • Ingress Protection: IP20
  • Communications: USB HID, RS-232 and RJ45 Ethernet IoT port
  • Software: WinPower and WinPower View app
  • External Battery Support: Up to 4 external battery modules
  • Dimensions (H x L x W): 318mm x 424mm x 192mm
  • Weight: 24 kg
Key Features
  • True online double conversion protection for sensitive equipment
  • Unity power factor delivers the full 2000W output at a 2kVA rating
  • Wide 160–300VAC input range at full load
  • Pure sinewave output suitable for servers, networking and communications equipment
  • Australian output sockets for local installations
  • LCD display provides operating and alarm information
  • USB HID monitoring without requiring software installation
  • RS-232, Ethernet IoT and optional SNMP, Modbus, AS400 and WLAN connectivity
  • Built-in over-voltage, fan-lock, over-temperature and overload warnings
  • External battery banks available for extended runtime
Professional Installation Requirements
  • Connection requires a suitable earthed 10A power point. Installation, commissioning and integration into critical IT or permanently connected electrical systems should be performed by a suitably qualified electrician in accordance with AS/NZS 3000 and the manufacturer's instructions.
Applications
  • Servers and server rooms
  • Network and telecommunications equipment
  • Storage and VoIP systems
  • Industrial control and automation equipment
  • Medical and laboratory equipment
  • Computers and other sensitive IT equipment
  • Critical communications infrastructure
Standards & Compliance
  • Applicable UPS safety standard: AS 62040.1:2019
  • Applicable UPS electromagnetic compatibility standard: AS 62040.2
  • Electrical installation requirements: AS/NZS 3000
Environmental Benefits
  • 93% double conversion efficiency helps reduce operating energy consumption
  • Optimised battery management is designed to extend battery service life
  • Replaceable internal batteries and optional external battery modules can extend product service life and reduce replacement waste
  • UPS batteries and electronic components should be recycled through approved e-waste and battery recycling channels
Warranty Information

No specific Chase Power warranty term was published on the manufacturer's product or catalogue pages located during research. Confirm applicable warranty coverage and battery warranty terms with Chase Power or the authorised distributor before purchase.

Available Now

Available through Chase Power and authorised Australian distributors, subject to distributor stock and project requirements.


UPS Sizing Calculator




This calculator follows relevant Australian standards to ensure reliable and compliant performance. It provides an estimated recommendation based on user inputs.
Users must verify specifications before purchasing.