Thermal Overload Relay 0.16-0.25A 25A Frame NR2 Chint
Chint NR2 thermal overload relay features 0.16-0.25A setting range, 25A frame, and direct mounting to NC1 contactors. Ideal for motor overload protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NR2-25 Motor Overload Relay, Thermal Motor Protection Relay, Overload Relay for NC1 Contactors
- Setting Current Range: 0.16–0.25 A
- Frame Size: 25 A
- Poles: 3
- Rated Operational Voltage: 380/400/415 V AC and 660 V AC
- Rated Insulation Voltage: 690 V
- Rated Impulse Withstand Voltage: 6 kV
- Tripping Class: 10A
- Auxiliary Contacts: 1 normally open plus 1 normally closed
- Thermal Current: 25 A
- Matched Fuse: 0.5 A aM or 0.5 A gG
- Operating Frequency: 50/60 Hz
- Mounting: Direct plug-in mounting or independent mounting with MB-2 base
- Connection: M4 main terminals and M3.5 auxiliary terminals
- Dimensions (H x L x W): 94mm x 66mm x 45mm
- Weight: 0.2 kg
- Adjustable 0.16–0.25 A motor overload protection
- Three-phase bimetal thermal protection
- Phase loss protection
- Temperature compensation for more consistent tripping performance
- Manual or automatic reset selection
- Integrated trip indicator
- Test and stop pushbuttons
- Direct mounting to compatible CHINT NC1 and NC7 contactors
- Electrically separated 1NO plus 1NC auxiliary contacts
- Suitable for continuous-duty AC motor control applications
- Installation and adjustment should be performed by a licensed electrician or suitably qualified controls technician. Select the setting to suit the motor full-load current and install with appropriate short-circuit protection in accordance with applicable wiring rules and manufacturer instructions.
- Overload protection for small three-phase AC motors
- Motor starters and control panels
- HVAC and refrigeration equipment motor circuits
- Pumps, fans and compressors
- Direct-mounted protection for CHINT NC1 contactor assemblies
- AS/NZS IEC 60947.4.1:2015 is the applicable Australian/New Zealand product standard for electromechanical contactors, motor-starters and associated overload relays; verify product-specific Australian conformity and RCM requirements before installation
- Installation should comply with AS/NZS 3000 where applicable
- Helps prevent motor damage and premature replacement by providing overload and phase-loss protection
- Temperature-compensated operation supports reliable equipment service life
- Replaceable relay construction can reduce waste compared with replacing a complete motor starter assembly
CHINT warranty policy specifies 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to applicable contract terms and conditions.
Available through authorised CHINT distributors in Australia.