Thermal Overload Relay 0.25-0.4A 25A Frame NR2 Chint
Chint NR2 thermal overload relay features 0.25-0.4A setting range, 25A frame, and direct mounting to NC1 contactors. Ideal for motor overload protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NR2-25-0.4 Thermal Relay, Motor Overload Relay, Thermal Motor Protection Relay
- Model: NR2-25-0.4
- Product Code: 268134
- Current Setting Range: 0.25-0.4A
- Frame Size: 25A
- Rated Operational Voltage: Up to 690V AC
- Rated Frequency: 50/60Hz
- Number of Poles: 3
- Tripping Class: 10A
- Auxiliary Contacts: 1NO + 1NC, electrically separated
- Protection Functions: Overload and phase-loss protection
- Reset Mode: Manual or automatic
- Mounting Type: Direct plug-in mounting or independent mounting with MB-2 base
- Compatible Contactors: CHINT NC1-09 to NC1-32, NC7-09 to NC7-32
- Contact Ratings: AC-15 2.73A at 220V or 1.58A at 380V; DC-13 0.2A at 220V
- Ambient Operating Temperature: -5°C to +40°C
- Installation Altitude: Up to 2,000m
- Terminal Screw: M3.5
- Recommended Fuse: 1A aM or 1A gG
- Dimensions (H x L x W): 93.6mm x 102mm x 45mm
- Weight: 0.9 kg
- Adjustable 0.25-0.4A motor protection range
- Provides overload and phase-failure protection for three-phase AC motors
- Directly mounts beneath compatible CHINT NC1 contactors
- Temperature compensation for consistent thermal tripping
- Manual and automatic reset selection
- Built-in test and stop buttons
- Visual trip indication
- Three-phase bimetal thermal design
- Suitable for direct-on-line motor starters
- Installation, adjustment and maintenance must be performed by a licensed electrician or suitably qualified technician with the supply isolated. Install in accordance with the manufacturer's instructions and AS/NZS 3000. Set the relay to the motor's nameplate full-load current and verify coordination with the contactor and short-circuit protection.
- Overload protection for small three-phase AC motors
- Direct-on-line motor starters
- HVAC and refrigeration equipment control panels
- Pumps, fans and compressors
- Industrial control cabinets using CHINT NC1 contactors
- Designed to IEC/EN 60947-4-1 for low-voltage contactors and motor starters incorporating thermal overload relays
- Electrical installation should comply with AS/NZS 3000
- Helps prevent premature motor failure, reducing replacement equipment and material waste
- Replaceable overload relay design supports repair rather than complete starter replacement
- Metal and plastic components can be separated and recycled through appropriate electrical waste channels
- Temperature compensation and accurate current adjustment help avoid unnecessary nuisance trips and associated energy losses
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus, including thermal overload relays, when purchased through authorised sales channels. Contract terms may vary.
Available through authorised CHINT distributors in Australia.