3kVA 2.4kW UPS Rack Tower Mount XL Plus Cabac
Cabac XL Plus UPS features 3kVA 2.4kW capacity, rack or tower mounting, smart software, and auto restart. Ideal for server and network equipment backup.
Sign in
Please login to continue to your account.
Alternatively Known As: XL Plus XL3-RT UPS, Cabac XL+ 3000VA UPS, 3kVA Line-Interactive UPS
- Model: XL3-RT
- Capacity: 3000VA / 2400W
- Topology: Pure sinewave line-interactive
- Input Voltage Range: 177–300VAC with automatic voltage regulation
- Output Voltage: 220V, 230V or 240V selectable
- Transfer Time: Typically 2–6ms
- Battery Type: Sealed maintenance-free lead-acid
- Battery Configuration: 4 x 12V 9Ah
- Recharge Time: Approximately 6–8 hours to 90%
- Output Connections: 2 x Australian 10A outlets, 3 x IEC 10A outlets and 1 x 15A IEC outlet
- Communications: USB standard; optional SNMP, RS232 and relay interfaces
- Protection: 1600J surge protection, network surge protection and resettable short-circuit protection
- Operating Temperature: 0–40°C
- Humidity: 0–90% RH, non-condensing
- Mounting: Convertible rack or tower installation
- Runtime Expansion: Compatible with EBXL+ external battery modules
- Dimensions (H x L x W): 132mm x 410mm x 440mm
- Weight: 26.7 kg
- Pure sinewave output for servers, networking equipment and other sensitive loads
- Rack/tower convertible enclosure for flexible installation
- Interactive LCD/LED status indication
- UPS Smart software supplied for monitoring, notifications and event logging
- Automatic restart when mains power returns after battery depletion
- Cold-start capability without an AC supply
- Extendable runtime using compatible EBXL+ battery modules
- Network surge protection for connected communications equipment
- Installation should be performed by a suitably qualified electrical or UPS technician. Follow the manufacturer’s installation instructions, provide the specified front and rear ventilation clearances, and ensure mains connection, earthing, rack mounting and commissioning comply with applicable Australian electrical requirements, including AS/NZS 3000 where relevant.
- Server and network equipment backup
- Telecommunications and data cabinets
- CCTV and security systems
- Industrial control equipment
- Roller doors, shutters and motor loads
- Medical and other sensitive electronic equipment
- AS 62040.1:2019 — applicable Australian safety standard for uninterruptible power systems; specific XL3-RT certification is not stated in the available product documentation. The available datasheet lists EN50091-1-1, EN50091-2 and C-Tick compliance references.
- AS/NZS 3000:2018 — relevant to any fixed electrical installation, isolation and earthing work associated with the UPS.
- Sealed lead-acid batteries can be recovered through authorised battery recycling programmes.
- Expandable EBXL+ battery modules can extend operating runtime and potentially delay replacement of the main UPS installation.
- Automatic voltage regulation and pure sinewave output can support reliable operation of connected equipment, reducing disruption-related equipment replacement.
- Replaceable battery architecture may extend the usable service life of the UPS and reduce electronic waste.
PSS standard return-to-base warranty: 2 years from the purchase date, subject to proof of purchase and the stated installation, operating and maintenance conditions. The warranty covers faulty materials or workmanship; transportation to the service base is generally the purchaser’s responsibility. ([pssdistributors.com.au](https://www.pssdistributors.com.au/ups-warranty/))
Available through Cabac and authorised Australian distributors. Confirm current stock and lead time before ordering; the Cabac product page advises customers to contact the distributor regarding availability. ([cabac.com.au](https://www.cabac.com.au/p/power-supplies-batteries/uninterruptible-power-supplies/line-interactive-ups/xl3-rt))
UPS Sizing Calculator
This calculator follows relevant Australian standards to ensure reliable and compliant performance. It provides an estimated recommendation based on user inputs.
Users must verify specifications before purchasing.