MCB 1P 32A 10kA B Curve DIN Rail NB1-63H Chint
Chint NB1-63H 1P 32A MCB features 10kA breaking capacity, B-curve thermal-magnetic protection and DIN rail mount to IEC 60898. For domestic and commercial boards.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NB1-63H B32 MCB, 32A Single-Pole Circuit Breaker, DIN Rail MCB
- Rated Current: 32 A
- Number of Poles: 1P
- Tripping Characteristic: B curve, 3–5 times rated current
- Rated Voltage: AC 230/400 V or 240/415 V
- Rated Frequency: 50/60 Hz
- Rated Short-Circuit Breaking Capacity: 10 kA
- Release Type: Thermal-magnetic
- Standard: IEC/EN 60898-1
- Rated Impulse Withstand Voltage: 6 kV
- Energy Limiting Class: 3
- Electrical Life: 10,000 operations
- Mechanical Life: 20,000 operations
- Terminal Capacity: Up to 25 mm² copper conductors
- Terminal Connection: Cable, U-type busbar or pin-type busbar
- Mounting: 35 mm DIN rail to EN 60715
- Connection: Top or bottom feed
- Protection Rating: IP20
- Operating Temperature: -25°C to +70°C
- Dimensions (H x L x W): 86mm x 78mm x 18mm
- Weight: 0.11 kg
- Provides overload and short-circuit protection
- B-curve operation suits general domestic and commercial circuits with relatively low inrush current
- High 10 kA short-circuit breaking capacity
- Single-pole modular design for compact distribution boards
- DIN rail mounting with fast-clip installation
- Suitable for cable and compatible busbar connections
- Positive isolation and switching function
- Auxiliary, shunt-release, under-voltage-release and alarm-contact accessories are available for the series
- Installation and maintenance must be performed by a licensed electrician or suitably qualified electrical professional. Install in accordance with AS/NZS 3000, the manufacturer's instructions and applicable local electrical regulations.
- Domestic consumer units and distribution boards
- Commercial switchboards
- Industrial control and distribution panels
- General lighting and socket-outlet circuits
- Overload and short-circuit protection for fixed electrical circuits
- AS/NZS 60898.1:2004 for circuit-breakers providing overcurrent protection in household and similar installations
- RCM/SAA approval applicable to the certified NB1-63H product range
- Metal and thermoplastic components can be separated and directed to appropriate electrical equipment recycling streams at end of life
- Long mechanical and electrical service life can reduce replacement frequency and associated material waste
- Designed for use in electrical distribution systems that support efficient and controlled power delivery
- Product materials should be disposed of through local electrical and industrial waste recycling processes
CHINT's general warranty policy covers other low-voltage apparatus for 27 months from the date of manufacture when purchased through authorised sales channels, subject to the applicable customer contract and warranty conditions.