MCB 1P 63A 10kA C Curve DIN Rail NB1-63H Chint
Chint NB1-63H 1P 63A MCB features 10kA breaking capacity, C-curve thermal-magnetic protection and DIN rail mount to IEC 60898. For domestic and commercial boards.
Sign in
Please login to continue to your account.
Alternatively Known As: 63A C-Curve MCB, Single-Pole DIN-Rail Circuit Breaker, Thermomagnetic Circuit Breaker
- Product Type: Miniature circuit breaker
- Poles: 1P
- Rated Current: 63 A
- Rated Voltage: AC 230/400–240/415 V
- Rated Frequency: 50/60 Hz
- Breaking Capacity: 10 kA
- Tripping Curve: C curve, 5–10 times rated current
- Insulation Voltage: 500 V
- Impulse Withstand Voltage: 6 kV
- Energy Limiting Class: 3
- Terminal Capacity: Up to 25 mm²
- Tightening Torque: 2.5 N·m
- Mounting: 35 mm EN 60715 DIN rail
- Connection: Top or bottom feed
- Protection Degree: IP20
- Mechanical Life: 20,000 operations
- Electrical Life: 10,000 operations
- Operating Temperature: −25°C to +70°C, with daily average not exceeding +35°C
- Standard: IEC/EN 60898-1
- Dimensions (H x L x W): 86mm x 78mm x 18mm
- Weight: 0.11 kg
- Thermal-magnetic overload and short-circuit protection
- C-curve operation suitable for resistive and inductive loads with moderate inrush current
- 10 kA rated short-circuit breaking capacity
- Single-pole modular design for residential, commercial and industrial distribution boards
- Fast-clip mounting on standard 35 mm DIN rail
- Accepts cable, U-type busbar and pin-type busbar connections
- Top or bottom electrical feed
- Compatible auxiliary, alarm, shunt-release and undervoltage accessories
- Installation, testing and commissioning should be carried out by a licensed electrician in accordance with AS/NZS 3000 and applicable local electrical regulations. Confirm fault levels, cable sizing, discrimination and local approval requirements before installation.
- Residential switchboards and consumer units
- Commercial distribution boards
- Industrial control and power distribution panels
- Overload and short-circuit protection for final subcircuits
- Protection of resistive and inductive loads with moderate starting current
- Applicable product standard: AS/NZS 60898.1:2024 for AC circuit-breakers used for household and similar installations
- Manufacturer documentation specifies IEC/EN 60898-1; verify Australian approval and RCM requirements before installation
- Installation should comply with AS/NZS 3000
- Long mechanical and electrical service life can reduce replacement frequency and associated waste
- Compact modular construction uses less switchboard space and material than larger circuit-breaker formats
- End-of-life separation of metal and polymer components can support responsible electrical-equipment recycling
CHINT general warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable contract and warranty conditions.
Available through authorised CHINT distributors in Australia.