Chint NB1-63H 1P 6A MCB features 10kA breaking capacity, C-curve thermal-magnetic protection and DIN rail mount to IEC 60898. For domestic and commercial boards.

Alternatively Known As: Miniature Circuit Breaker, Single-Pole MCB, DIN Rail Circuit Breaker, Thermal-Magnetic Circuit Breaker

Technical Specifications
  • Rated Current: 6 A
  • Number of Poles: 1P
  • Rated Voltage: 230 V AC
  • Rated Frequency: 50/60 Hz
  • Breaking Capacity: 10 kA
  • Tripping Curve: C curve
  • Protection Type: Thermal-magnetic overload and short-circuit protection
  • Insulation Voltage: 500 V
  • Impulse Withstand Voltage: 6 kV
  • Energy Limiting Class: 3
  • Protection Degree: IP20
  • Terminal Connection: Cable, U-type busbar or pin-type busbar
  • Mounting: 35 mm EN 60715 DIN rail
  • Electrical Life: 4,000 cycles
  • Mechanical Life: 20,000 cycles
  • Dimensions (H x L x W): 86mm x 78mm x 18mm
  • Weight: 0.11 kg
Key Features
  • Single-pole circuit protection for low-voltage AC installations
  • C-curve characteristic suited to mixed loads and circuits with moderate inrush current
  • 10kA rated short-circuit breaking capacity
  • Thermal-magnetic protection against overloads and short circuits
  • DIN rail mounting with fast-clip installation
  • Contact position indication
  • Top and bottom connection capability
  • Suitable for domestic, commercial and light industrial distribution boards
Professional Installation Requirements
  • Installation, testing and commissioning should be performed by a licensed electrician in accordance with AS/NZS 3000 and applicable local requirements. Confirm fault level, cable size, discrimination and product approval before installation.
Applications
  • Domestic distribution boards
  • Commercial switchboards
  • Lighting circuits
  • Socket-outlet and general-purpose circuits
  • Control circuits and small motor loads with suitable inrush characteristics
  • Low-voltage AC final circuit protection
Standards & Compliance
  • Product documentation specifies IEC/EN 60898-1. AS/NZS 60898.1:2024 is the applicable Australian/New Zealand standard for household and similar AC circuit-breakers; verify the specific unit's Australian approval and RCM marking before installation.
Environmental Benefits
  • Durable construction and long mechanical life can reduce replacement frequency and associated waste
  • Thermal-magnetic protection helps prevent damage to downstream wiring and equipment, reducing premature replacement
  • Compact DIN rail format supports modular installation and easier component replacement
Warranty Information

CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus, subject to authorised sales channels, correct installation, operation and the policy's terms and exclusions.

Available Now

Available through authorised CHINT distributors in Australia.