Chint NB1-63H 2P 20A MCB features 10kA breaking capacity, C-curve thermal-magnetic protection and DIN rail mount to IEC 60898. For domestic and commercial boards.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NB1-63H/C20-2P-10 MCB, 2P C20 MCB, 20A Double-Pole Circuit Breaker
- Product Type: Miniature circuit breaker with thermal-magnetic protection
- Number of Poles: 2P
- Rated Current: 20 A
- Tripping Curve: C curve, 5–10 times rated current
- Rated Voltage: 230/400–240/415 V AC
- Rated Frequency: 50/60 Hz
- Short-Circuit Breaking Capacity: 10 kA
- Reference Standard: IEC/EN 60898-1
- Insulation Voltage: 500 V
- Energy-Limiting Class: Class 3
- Protection Degree: IP20
- Mounting: 35 mm EN 60715 DIN rail
- Connection: Top or bottom feed
- Terminal Capacity: Up to 25 mm²
- Tightening Torque: 2.5 N·m
- Mechanical Life: Up to 20,000 operations
- Electrical Life: Up to 10,000 operations
- Product Code: 179828
- Dimensions (H x L x W): 86mm x 78mm x 36mm
- Weight: 0.3 kg
- Protects circuits against overload and short-circuit currents
- C-curve operation suits general domestic, commercial and mixed-load applications
- 2-pole switching for simultaneous isolation of active and neutral conductors where applicable
- 10 kA short-circuit breaking capacity
- Compact two-module DIN-rail format
- Compatible with cable, pin-type busbar and U-type busbar connections
- Top or bottom cable entry
- Optional auxiliary, alarm, shunt-release, under-voltage and residual-current accessories are available for the NB1 range
- Installation, testing and commissioning must be carried out by a licensed electrician in accordance with AS/NZS 3000 and the manufacturer's instructions. Confirm prospective fault current, discrimination, conductor sizing and suitability for the intended switchboard before installation.
- Domestic consumer units and distribution boards
- Commercial electrical switchboards
- Industrial control and power distribution panels
- Protection of general-purpose lighting and power circuits
- DIN-rail electrical enclosures and modular switchgear assemblies
- IEC/EN 60898-1 product standard stated for the breaker
- AS/NZS 60898.1:2024 is the applicable Australian/New Zealand product standard for household and similar AC circuit-breakers; specific AS/NZS certification for this item should be confirmed before Australian installation
- Installation is subject to AS/NZS 3000 wiring requirements
- Thermal-magnetic protection can limit fault damage and help extend the service life of connected wiring and equipment
- Class 3 energy limitation helps reduce let-through energy during short-circuit events
- Durable modular construction can reduce replacement frequency and electrical equipment waste
- Metal and thermoplastic components may be recoverable through appropriate electrical equipment recycling streams
CHINT's general warranty policy states 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable contract and warranty terms.