Chint NB1-63 2P 20A MCB features 6kA breaking capacity, C-curve thermal-magnetic protection and DIN rail mount to IEC 60898. For domestic and commercial boards.

Alternatively Known As: NB1-63 2P C20 MCB, 20A Double-Pole Circuit Breaker, DIN Rail MCB, Thermal-Magnetic Circuit Breaker

Technical Specifications
  • Rated Current: 20 A
  • Number of Poles: 2P
  • Tripping Curve: C curve, 5–10 In
  • Rated Voltage: 400 V AC for 2-pole configuration
  • Rated Frequency: 50/60 Hz
  • Breaking Capacity: 6 kA Icn and Ics
  • Insulation Voltage: 500 V Ui
  • Impulse Withstand Voltage: 4 kV Uimp
  • Mounting: TH35-7.5 DIN rail
  • Connection: Top or bottom feed
  • Terminal Capacity: 1–25 mm²
  • Terminal Tightening Torque: 2.0 N·m
  • Ingress Protection: IP20
  • Mechanical Life: 20,000 operations
  • Electrical Life: 4,000 operations
  • Operating Temperature: -5 °C to +40 °C
  • Dimensions (H x L x W): 82mm x 75.5mm x 36mm
  • Weight: 0.4 kg
Key Features
  • Thermal-magnetic protection against overload and short-circuit faults
  • C-curve characteristic suited to mixed loads and circuits with moderate starting currents
  • Two-pole switching for simultaneous disconnection of active and neutral conductors where required
  • Compact modular design for domestic, commercial and light-industrial distribution boards
  • DIN rail mounting for straightforward installation in compatible switchboards
  • Top or bottom cable entry for flexible board layouts
  • Compatible with selected CHINT auxiliary, alarm, shunt-release and undervoltage accessories
Professional Installation Requirements
  • Installation and connection to mains wiring must be performed by a licensed electrician in accordance with AS/NZS 3000 and applicable local requirements. Confirm prospective fault current, discrimination and conductor protection before installation.
Applications
  • Domestic distribution boards
  • Commercial switchboards
  • Light-industrial control and distribution panels
  • Overload and short-circuit protection for final subcircuits
  • Isolation of low-voltage AC circuits
Standards & Compliance
  • Applicable product standard: AS/NZS 60898.1:2024 for circuit-breakers for overcurrent protection in household and similar AC installations
  • Installation should comply with AS/NZS 3000 Wiring Rules
  • Manufacturer specification is listed to IEC/EN 60898-1; verify the supplied unit has the required Australian regulatory marking and approvals before installation
Environmental Benefits
  • Long mechanical and electrical service life can reduce replacement frequency and associated waste
  • Metal components and thermoplastics may be recoverable through appropriate electrical equipment recycling streams
  • REACH-related substance information is available for the NB1-63 series
Warranty Information

CHINT warranty policy provides 27 months from the date of manufacture against defects in materials and workmanship for other low-voltage apparatus sold through authorised sales channels, subject to applicable contract terms.

Available Now

Available through authorised CHINT distributors in Australia.