MCB 2P 50A 10kA C Curve DIN Rail NB1-63H Chint

BRAND: CABAC
SKU: 179834
$22.70 List price: $30.20
+
Chint NB1-63H 2P 50A MCB features 10kA breaking capacity, C-curve thermal-magnetic protection and DIN rail mount to IEC 60898. For domestic and commercial boards.

Alternatively Known As: 2 Pole MCB, C50 Circuit Breaker, DIN Rail Circuit Breaker, Thermal-Magnetic Circuit Breaker

Technical Specifications
  • Rated Current: 50 A
  • Number of Poles: 2P
  • Tripping Characteristic: C curve
  • Breaking Capacity: 10 kA Icn; 7.5 kA Ics
  • Rated Voltage: 400/415 V AC
  • Rated Frequency: 50/60 Hz
  • Insulation Voltage: 500 V
  • Impulse Withstand Voltage: 6 kV
  • Energy Limiting Class: 3
  • Mounting: EN 60715 35 mm DIN rail
  • Connection: Top or bottom feed
  • Protection Type: Thermal-magnetic overload and short-circuit protection
  • Dimensions (H x L x W): 86mm x 78mm x 36mm
  • Weight: 0.25 kg
Key Features
  • Two-pole protection and switching for single-phase distribution circuits
  • C-curve magnetic tripping characteristic for resistive and inductive loads with moderate inrush current
  • 10 kA rated short-circuit breaking capacity
  • Thermal-magnetic protection against overload and short-circuit currents
  • Compatible with 35 mm DIN rail mounting
  • Suitable for domestic, commercial and light industrial distribution boards
  • Front-facing toggle for circuit isolation and manual operation
Professional Installation Requirements
  • Installation and connection must be performed by a licensed electrician in accordance with applicable Australian electrical requirements. Select cable size, protection and fault ratings to suit the installation.
Applications
  • Domestic switchboards and distribution boards
  • Commercial electrical distribution panels
  • Light industrial control and power distribution boards
  • Protection of resistive and inductive final circuits
  • DIN rail-mounted electrical enclosures
Standards & Compliance
  • Global-Mark certification for the NB1-63H range to AS/NZS 60898.1:2004, including the 2P C50 configuration
  • Installation should comply with the applicable requirements of AS/NZS 3000
Environmental Benefits
  • RoHS declaration available for the NB1-63H product range
  • Durable reusable switchgear construction can reduce replacement waste over the service life of an electrical installation
  • Metal and thermoplastic components may be recoverable through appropriate electrical equipment recycling processes
Warranty Information

27 months from the date of manufacture for other CHINT low-voltage apparatus when purchased through authorised sales channels; contract terms may vary.