MCB 2P 63A 6kA C Curve DIN Rail NB1-63 Chint
Chint NB1-63 2P 63A MCB features 6kA breaking capacity, C-curve thermal-magnetic protection and DIN rail mount to IEC 60898. For domestic and commercial boards.
Sign in
Please login to continue to your account.
Alternatively Known As: 2P 63A MCB, Double-Pole Circuit Breaker, DIN Rail MCB, C63 Miniature Circuit Breaker
- Rated Current: 63 A
- Number of Poles: 2P
- Tripping Curve: C curve, 5–10 In magnetic operation range
- Rated Voltage: 400 V AC
- Rated Frequency: 50/60 Hz
- Breaking Capacity: 6 kA
- Insulation Voltage: 500 V
- Impulse Withstand Voltage: 4 kV
- Connection Capacity: 1–25 mm² conductors
- Terminal Tightening Torque: 2.0 N·m
- Mounting: TH35-7.5 DIN rail
- Protection Degree: IP20
- Mechanical Life: 20,000 operations
- Electrical Life: 4,000 operations
- Operating Temperature: -5°C to +40°C
- Feed Direction: Top or bottom connection
- Dimensions (H x L x W): 86mm x 78mm x 36mm
- Weight: 0.2 kg
- Thermal-magnetic protection against overload and short-circuit currents
- Two-pole switching and isolation for low-voltage distribution circuits
- C-curve characteristic suited to mixed loads, socket circuits and small motors
- 6 kA rated short-circuit breaking capacity
- Compatible with selected CHINT auxiliary, alarm, shunt-release and undervoltage accessories
- Compact two-module DIN rail format
- Installation and connection should be performed by a licensed electrician in accordance with AS/NZS 3000 and the switchboard manufacturer's requirements. Confirm prospective fault current, conductor sizing, discrimination and enclosure suitability before installation.
- Residential distribution boards
- Commercial electrical switchboards
- Light industrial power distribution
- Mixed-load circuits with moderate starting currents
- Circuit isolation and overcurrent protection in DIN rail enclosures
- Applicable Australian/New Zealand product standard: AS/NZS 60898.1 for miniature circuit-breakers for a.c. operation
- Manufacturer-stated design standard: IEC/EN 60898-1
- Long mechanical and electrical service life can reduce replacement frequency and product waste
- Effective overload and short-circuit protection can help prevent damage to downstream electrical equipment
- Compact DIN rail design supports efficient switchboard use and material utilisation
CHINT warranty policy states that other low-voltage apparatus is covered against defects in materials and workmanship for 27 months from the date of manufacture when sold through authorised channels; contractual terms may vary.
Available through authorised CHINT distributors in Australia.