- Rated Current: 10 A
- Number of Poles: 3P
- Tripping Characteristic: C curve, 5–10 times rated current
- Rated Voltage: AC 230/400–240/415 V
- Short-Circuit Breaking Capacity: 10 kA
- Rated Insulation Voltage: 500 V
- Rated Frequency: 50/60 Hz
- Energy Limiting Class: 3
- Rated Impulse Withstand Voltage: 6 kV
- Terminal Capacity: Up to 25 mm²
- Tightening Torque: 2.5 N·m
- Protection Degree: IP20
- Operating Temperature: −25 °C to +70 °C
- Mechanical Life: 20,000 operations
- Electrical Life: 10,000 operations
- Mounting: 35 mm DIN rail to EN 60715
- Connection: Top or bottom feed
- Dimensions (H x L x W): 86mm x 78mm x 54mm
- Weight: 0.39 kg
- Three-pole protection for three-phase AC circuits
- Thermal-magnetic protection against overload and short-circuit faults
- C-curve operation suitable for circuits with moderate inrush currents
- 10 kA short-circuit breaking capacity
- Compact three-module DIN rail format
- Compatible with cable, U-type busbar and pin-type busbar connections
- Optional auxiliary, alarm, shunt-release and under-voltage accessories available
- Installation, testing and commissioning should be performed by a licensed electrician in accordance with applicable electrical installation requirements, including AS/NZS 3000. Confirm fault levels, cable sizing, discrimination and local approval requirements before installation.
- Residential distribution boards
- Commercial switchboards
- Industrial control and distribution panels
- Three-phase lighting and power circuits
- Protection of motors and equipment with moderate starting currents
- AS/NZS 60898.1 is the applicable Australian/New Zealand standard series for miniature circuit-breakers of this type; verify model-specific approval and RCM requirements before installation.
- Long mechanical and electrical service life can reduce replacement frequency and material waste
- Energy-limiting Class 3 design helps limit fault energy during short-circuit interruption
- Metal and thermoplastic components may be recyclable through appropriate electrical equipment recycling streams