Safety I O Module FX3-XTDI80012 SIL 3 & Category 4 8 Safety Inputs SICK
The Safety I O Module FX3-XTDI80012 is designed for industrial automation safety systems, featuring SIL 3 safety integrity and Category 4 compliance.
Sign in
Please login to continue to your account.
- Safety integrity level: SIL 3 (IEC 61508)
- Category: 4 (EN ISO 13849)
- Performance level: PL e (EN ISO 13849)
- Mean probability of dangerous failure per hour (PFHD): 0.4 x 10^-9
- Mission time: 20 years
- Number of safety inputs: 8
- Number of test outputs: 8
- Connection type: Plug-in spring terminals
- Protection class: III (EN 61140)
- Voltage supply: Via FLEXBUS+
- Internal power consumption: ≤ 2 W
- Input voltage HIGH: 13 V DC to 30 V DC
- Input voltage LOW: –5 V DC to 5 V DC
- Input current HIGH: 2.4 mA to 3.8 mA
- Input current LOW: –2.5 mA to 2.1 mA
- Test outputs voltage supply: Via FLEXBUS+
- Type of output: PNP semiconductors, short-circuit protected
- Test pulse generator: 2
- Output voltage HIGH: 15 V DC to 30 V DC
- Output current: ≤ 120 mA
- Enclosure rating: IP20 (EN 60529)
- Ambient operating temperature: –25 °C to +55 °C
- Storage temperature: –25 °C to +70 °C
- Air humidity: ≤ 95%, Non-condensing
- Single gas resistance (sulfur dioxide): 25 ppm, 21 days, 25 °C
- Mixed gas resistance: 100 ppb H2S, 2000 ppb NO2, 100 ppb Cl2, 2000 ppb SO2, 21 days, 30 °C
- Dimensions (H x L x W): 96.5mm x 120.6mm x 22.5mm
- Weight: 0.139 kg
- I/O module configurable via Flexi Soft Designer software
- Protective coating for resistance to sulfur and challenging ambient conditions
- Safety integrity level SIL 3 (IEC 61508)
- Category 4 and Performance Level e (EN ISO 13849)
- 8 safety inputs and 8 test outputs with plug-in spring terminals
- Flexi Loop-compatible
- Short-circuit protected PNP semiconductor outputs
- Low internal power consumption (≤ 2 W)
- Wide ambient operating temperature range from –25 °C to +55 °C
- IP20 enclosure rating
- Installation should be performed by qualified personnel familiar with industrial safety systems and electrical standards.
- Industrial automation safety systems
- Machine safety monitoring
- Hazardous environment control requiring sulfur resistance
- AS/NZS 4801 – Occupational Health & Safety Management Systems
- Protective coating extends product lifespan reducing waste
- Low power consumption minimizes energy use
Standard manufacturer warranty applies; please refer to SICK for specific warranty terms.
The SICK FX3-XTDI80012 I/O Safety Module is available for immediate purchase, ideal for industrial safety and automation applications requiring high reliability and environmental resistance.